Turbine Meter

Elgas radial-blade turbine gas meter Elgas radial-blade turbine gas meter diagram
Load range Operating pressure Pulse generator
DN
[mm]
Size Qmin
[m3/hr]
Qmax
[m3/hr]
P
[bar]
LF
(Standard)
1 imp. =m3
2nd LF
(Standard)
1 pulse, =m3
MF
(Option)
1 pulse, =m3
HF
(Option)approx. f
at Q max [Hz]
50 G 16 3 25 6 1 1 0.01 350
50 G 25 4 40 6 1 1 0.01 550
50 G 40 5 65 6 1 1 0.01 850
50 G 65 6 100 6 1 1 0.01 1300
50 G 100 10 160 6 1 1 0.01 1300
80 G 65 10 100 6 1 1 0.01 200
80 G 100 12 160 6 1 1 0.01 320
80 G 160 15 250 6 1 1 0.01 500
80 G 250 20 400 6 1 1 0.01 800
100 G 100 13 160 6 1 1 0.01 280
100 G 160 15 250 6 1 1 0.01 440
100 G 250 20 400 6 1 1 0.01 380
100 G 400 25 650 6 1 1 0.01 610
Catalog
download icon

APPLICATION

  • Principle of velocity measurement
  • For measurements requiring obligatory verification
  • Accuracy:
    • from 0.2 Qmax to Qmax… +/- 1,5 %
    • below 0.2 Qmax… +/- 2 %
  • Sizes G 16 up to F 400
  • Dimentions DN 40, 50, 80 and 100
  • Operating Pressure max. 6 bar
  • Meter element can be calibrated without monopipe fitting
  • Counting device is in a gas-free space
  • Low starting value
  • High measurement stability and operational security due to high-quality, wear-resistant components
  • Self-lubricating ball bearings
  • Pressure extraction connection inside the meter
  • Designed for simple servicinf (measurement-catridge principle)
  • LF-pulse generator (standard)
  • Standard integrated flow stainer
  • Short straight inlet lengths (2 x DN)
  • Operation temperature range:
    • gas temperature -10°C up to +60°C
    • ambient temperature -10°C up to +60°C